Instructions for installing the Gateway, Thermostats and remote temp sensors.

🪛 Gateway Installation

1. Locate the network room or manager’s office. Install the mounting plate in location with access to power and network. Preferably having the top of the gateway pointing towards the location of where the other EMS equipment will be. Mount gateway to plate with connectors to the right and lights to the left (Putting the power port and Ethernet port on top). Plug in the power cord into the wall outlet then plug the cat 5 cable provided into the designated port on the switch. Insert the CAT-5 patch cord into the ethernet port and then install the power cord into the gateway.

  1. Gateway will have all lights blinking then Link light will flash red/orange and then the middle light will be green.

  2. Open installer app (Instruction in prior to install section) and Press the green button “+ add Device”.

  3. You will select the gateway and tap green “continue” button. On this page you can enter the middle five numbers in the box labeled “center digits” and the last four in box labeled “last 4 digits

  4. Then tap on the button that says “Name” and enter “Gateway <center number>”

  5. Take photos of the gateway placement and port connected.

image-20240412-142033.png
image-20240412-140919.png

🪛 SmartStat Thermostat Installation

  1. Disconnect each existing thermostat and connect the SmartStat thermostat.

  2. Commission each thermostat within the mobile app

    • 📲 Include specific labeling like RTU-1 Front or something that matches customer naming conventions
  3. Make sure Mechanical settings are set the same as the old stat.

  4. Test each thermostat.

    • 🌡️ Use temperature gun to verify heat working, cooling working at each
    • 📸 Record measurements and take photos
    • 📝 Label each thermostat with provided sticker
  5. Note if remote sensors are in use

🪛 Remote Sensors

This part of the install typically requires a tall ladder or a manual/powered man lift

  1. Locate ductworks, specifically which ducts are closest to the supply

    • 🚨 If there are hard ceilings - go to alternate solutions
  2. Run Cat5e (ethernet cable) at ceiling height along ductwork

    • (info) All Cat5e runs must homerun to either gateway or wireless sensor pod
  3. Connect temperature lead to Cat5e

    • 📝 Label temperature sensor with rooftop unit name using provided sticker
  4. Insert into ductwork, ensuring metal lead does not touch the exterior of ductwork

    • (info) Ensure that sensor is all the way into the duct and tip is not in contact with the metal duct
  5. Document each temperature sensor location with photos in the Installation app

    • 📸 Close up photo should capture the label and wide angle should capture the location
  6. Locate existing remote sensors, swap with provide 10K Ohm thermistors

    • 📲 Verify connect of remote sensors at the thermostat and in mobile app
    • 🌡️ Verify with heat gun that temperatures match what is record in app

Hard ceiling Option 1 - access rooftop units via rooftop

  1. Install wireless temperature module

  2. attached temperature leads

  3. drop into plenum

  • No labels