Instructions for installing the Gateway, Thermostats and remote temp sensors.
Install Gateway in network room or manager’s office, according to predetermined placement and network port.
Validate gateway comes online and connects to cloud.
Take photos of the gateway placement and port connected.
Disconnect each existing thermostat and connect the SmartStat thermostat.
Commission each thermostat within the mobile app
Make sure Mechanical settings are set the same as the old stat.
Test each thermostat.
Note if remote sensors are in use
This part of the install typically requires a tall ladder or a manual/powered man lift |
Locate ductworks, specifically which ducts are closest to the supply
Run Cat5e (ethernet cable) at ceiling height along ductwork
Connect temperature lead to Cat5e
Insert into ductwork, ensuring metal lead does not touch the exterior of ductwork
Document each temperature sensor location with photos in the Installation app
Locate existing remote sensors, swap with provide 10K Ohm thermistors
Hard ceiling Option 1 - access rooftop units via rooftop
|