Instructions for installing the Gateway,
...
Table of Contents | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
🪛 Gateway Installation
1. Locate the network room or manager’s office. Install the mounting plate in location with access to power and network. Preferably having the top of the gateway pointing towards the location of where the other EMS equipment will be. Mount gateway to plate with connectors to the right and lights to the left (Putting the power port and Ethernet port on top). Plug in the power cord into the wall outlet then plug the cat 5 cable provided into the designated port on the switch. Insert the CAT-5 patch cord into the ethernet port and then install the power cord into the gateway.
Gateway will have all lights blinking then Link light will flash red/orange and then green. The Middle light will show green and then validate gateway comes online and connects to the cloud by opening install app (extend
Take photos of the gateway placement and port connected.
...
Thermostat
...
Disconnect each existing thermostat and connect the SmartStat thermostat.
Commission each thermostat within the mobile app
- 📲 Include specific labeling like RTU-1 Front or something that matches customer naming conventions
Make sure Mechanical settings are set the same as the old stat.
Test each thermostat.
- 🌡️ Use temperature gun to verify heat working, cooling working at each
- 📸 Record measurements and take photos
- 📝 Label each thermostat with provided sticker
Note if remote sensors are in use
🪛 Remote Sensors
Info |
---|
This part of the install typically requires a tall ladder or a manual/powered man lift |
Locate ductworks, specifically which ducts are closest to the supply
- 🚨 If there are hard ceilings - go to alternate solutions
Run Cat5e (ethernet cable) at ceiling height along ductwork
- All Cat5e runs must homerun to either gateway or wireless sensor pod
Connect temperature lead to Cat5e
- 📝 Label temperature sensor with rooftop unit name using provided sticker
Insert into ductwork, ensuring metal lead does not touch the exterior of ductwork
- Ensure that sensor is all the way into the duct and tip is not in contact with the metal duct
Document each temperature sensor location with photos in the Installation app
- 📸 Close up photo should capture the label and wide angle should capture the location
Locate existing remote sensors, swap with provide 10K Ohm thermistors
- 📲 Verify connect of remote sensors at the thermostat and in mobile app
- 🌡️ Verify with heat gun that temperatures match what is record in app
...
panelIconId | 1f6a8 |
---|---|
panelIcon | :rotating_light: |
panelIconText | 🚨 |
bgColor | #EAE6FF |
Hard ceiling Option 1 - access rooftop units via rooftop
...
Install wireless temperature module
...
attached temperature leads
...
, Duct Sensor, Energy Monitor and WiTemp+.